Figure 9-27 Installing a fastener
When laying out the water detection cable, ensure that the water detector is close to the
integrated cabling cabinet as to facilitate further cable connections.
Step 6 Place the water detection cable onto the fastener, secure the fastener, and keep the water
detection cable in close contact with the floor, as shown in
Figure 9-28 Securing a water detection cable
----End
Follow-up Procedure

9.1.12 Installing the WCON-22Z Skylight Ceiling Controller

Prerequisites
This section describes how to install the skylight ceiling controller on the outer surface of the
controlled skylight ceiling.
Issue 02 (2015-06-30)
If several water detection cables are connected in series, connect the male connector of one cable to the
female connector of another cable.
For air supplied from under the floor: Stand the water detector out of the raised floor or
base to facilitate further cable connections.
For air supplied horizontally: Place the water detector on the floor to facilitate further
cable connections.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9 Installing Auxiliary Devices
Figure
9-28.