Battery cable
Figure 10-32 Conceptual diagram of battery cable connections
Configuration 8
Configuration 8 applies to the scenario where the actual total power is greater than 36 kW but
no greater than 48 kW, and the backup time is 30 minutes. The following table describes
battery cabinet configuration.
Table 10-9 Battery cabinet configuration 8
Component
Battery
Issue 02 (2015-06-30)
Configuration
Pyromagnetic Breaker, 380
V AC/500 V DC, 125 A, 4P,
36 kA, 102 (W)*70 (D)*130
(H)
Battery Accessory, SD-480
V 100 Ah/12 V-PX-25 (ET),
Cables for battery group
SHOTO 6-GFM-100
embedded in battery cabinet
of IDC (25 mm
special
Configuration
Rechargeable Battery 480
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Configuration Number
1 PCS
2
), IDC
Configuration Number
A string of 40 batteries