Parameter Descriptions
[51]
MCO
Active when an MCO 302 or MCO 305 is
controlled
connected. The output is controlled from
option.
[55]
Pulse output
[60]
Comparator 0
See parameter group 13-1* Comparators. If
Comparator 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[61]
Comparator 1
See parameter group 13-1* Comparators. If
Comparator 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[62]
Comparator 2
See parameter group 13-1* Comparators. If
Comparator 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[63]
Comparator 3
See parameter group 13-1* Comparators. If
Comparator 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[64]
Comparator 4
See parameter group 13-1* Comparators. If
Comparator 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[65]
Comparator 5
See parameter group 13-1* Comparators. If
Comparator 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[70]
Logic Rule 0
See parameter group 13-4* Logic Rules. If
Logic Rule 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[71]
Logic Rule 1
See parameter group 13-4* Logic Rules. If
Logic Rule 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[72]
Logic Rule 2
See parameter group 13-4* Logic Rules. If
Logic Rule 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[73]
Logic Rule 3
See parameter group 13-4* Logic Rules. If
Logic Rule 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[74]
Logic Rule 4
See parameter group 13-4* Logic Rules. If
Logic Rule 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[75]
Logic Rule 5
See parameter group 13-4* Logic Rules. If
Logic Rule 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[80]
SL Digital
See parameter 13-52 SL Controller Action.
Output A
The output goes high whenever the Smart
Logic Action [38] Set dig. out. A high is
executed. The output goes low whenever
the Smart Logic Action[32] Set dig. out. A
low is executed.
[81]
SL Digital
See parameter 13-52 SL Controller Action.
Output B
The input goes high whenever the Smart
Logic Action [39] Set dig. out. B high is
executed. The input goes low whenever
the Smart Logic Action [33] Set dig. out. B
low is executed.
[82]
SL Digital
See parameter 13-52 SL Controller Action.
Output C
The input goes high whenever the Smart
Logic Action [40] Set dig. out. C high is
executed. The input goes low whenever
®
VLT
AutomationDrive FC 301/302 Programming Guide
[83]
SL Digital
Output D
[84]
SL Digital
Output E
[85]
SL Digital
Output F
[90]
kWh counter
pulse
[120] Local referen-
ce active
[121] Remote
reference
active
[122] No alarm
MG33MI02 - Rev. 2013-11-20
the Smart Logic Action [34] Set dig. out. C
low is executed.
See parameter 13-52 SL Controller Action.
The input goes high whenever the Smart
Logic Action [41] Set dig. out. D high is
executed. The input goes low whenever
the Smart Logic Action [35] Set dig. out. D
low is executed.
See parameter 13-52 SL Controller Action.
The input goes high whenever the Smart
Logic Action [42] Set dig. out. E high is
executed. The input goes low whenever
the Smart Logic Action [36] Set dig. out. E
low is executed.
See parameter 13-52 SL Controller Action.
The input goes high whenever the Smart
Logic Action [43] Set dig. out. F high is
executed. The input goes low whenever
the Smart Logic Action [37] Set dig. out. F
low is executed.
Sends a pulse (200 ms pulse width) to
output terminal whenever kWh counter
changes (15-02 kWh Counter).
Output is high when
parameter 3-13 Reference Site = [2] Local or
when parameter 3-13 Reference Site = [0]
Linked to hand auto at the same time as
the LCP is in Hand On mode.
Reference site
Local
Remote
set in
referen
reference
parameter 3-13
ce
Reference Site
active
[120]
Reference site:
1
Local
parameter 3-13 Ref
erence Site [2]
Reference site:
0
Remote
parameter 3-13 Ref
erence Site [1]
Reference site:
Linked to Hand/
Auto
Hand
1
Hand ⇒ off
1
Auto ⇒ off
0
Auto
0
Table 3.19 Local Reference Active
Output is high when
parameter 3-13 Reference Site = [1] Remote
or [0] Linked to hand/auto while the LCP is
in Auto on mode. See above.
Output is high when no alarm is present.
3
3
active
[121]
0
1
0
0
0
1
87