How to Programme
3.
Select [2] Initialisation
4.
Press [OK]
5.
Disconnect the mains supply and wait until the
display turns off.
6.
Reconnect the mains supply - the frequency
converter is now reset.
14-22 Operation Mode initialises all except:
Parameter 14-50 RFI Filter
8-30 Protocol
Parameter 8-31 Address
Parameter 8-32 FC Port Baud Rate
Parameter 8-35 Minimum Response Delay
Parameter 8-36 Max Response Delay
Parameter 8-37 Max Inter-Char Delay
Parameter 15-00 Operating hours to
parameter 15-05 Over Volt's
Parameter 15-20 Historic Log: Event to
parameter 15-22 Historic Log: Time
Parameter 15-30 Fault Log: Error Code to
parameter 15-32 Alarm Log: Time
Manual initialisation
1.
Disconnect from mains and wait until the display
turns off.
2.
2a
Press [Status] - [Main Menu] - [OK] at
the same time while power up for LCP
102, Graphical Display
2b
Press [Menu] - [OK] while power up for
LCP 101, Numerical Display
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed
according to default settings.
This procedure initialises all except:
Parameter 15-00 Operating hours
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
NOTICE
A manual initialisation also resets serial communication,
RFI filter settings (parameter 14-50 RFI Filter) and fault
log settings.
®