Parameter Descriptions
3-92 Power Restore
Option: Function:
[0] Off Resets the Digital Potentiometer reference to 0% after
power up.
[1] On
Restores the most recent Digital Potentiometer
reference at power up.
3-93 Maximum Limit
Range:
Function:
100 %
[-200 - 200
Set the maximum permissible value for
*
%]
the resultant reference. This is advisable if
the Digital Potentiometer is used for fine
tuning of the resulting reference.
3-94 Minimum Limit
Range:
Function:
-100 %
[-200 - 200
Set the minimum permissible value for
*
%]
the resultant reference. This is advisable if
the Digital Potentiometer is used for fine
tuning of the resulting reference.
3-95 Ramp Delay
Range:
Function:
Size
[ 0 -
Enter the delay required from activation of
related
0 ]
the digital potentiometer function until the
*
frequency converter starts to ramp the
reference. With a delay of 0 ms, the reference
starts to ramp as soon as INCREASE/DECREASE
is activated. See also parameter 3-91 Ramp
Time.
®