1.6.2 Pulse Start/Stop
Terminal 18 = 5-10 Terminal 18 Digital Input, [9] Latched
start.
Terminal 27= 5-12 Terminal 27 Digital Input, [6] Stop inverse.
Terminal 37 = Safe Torque Off (where available).
12
13
18
19
27
29
32
Start
Stop inverse
Speed
Start (18)
Start (27)
Illustration 1.7 Pulse Start/Stop
1.6.3 Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 = 5-10 Terminal 18 Digital Input [9]
Start (default)
Terminal 27 = 5-12 Terminal 27 Digital Input [19]
Freeze reference
Terminal 29 = 5-13 Terminal 29 Digital Input [21]
Speed up
Terminal 32 = 5-14 Terminal 32 Digital Input [22]
Speed down
NOTICE
Terminal 29 only in FC x02 (x=series type).
®
VLT
AutomationDrive FC 301/302 Programming Guide
33
20
37
Safe Stop
MG33MI02 - Rev. 2013-11-20
Illustration 1.8 Speed Up/Down
1.6.4 Potentiometer Reference
Voltage reference via a potentiometer
Reference Source 1 = [1] Analog input 53 (default)
Terminal 53, Low Voltage = 0 V
Terminal 53, High Voltage = 10 V
Terminal 53, Low Ref./Feedback = 0 RPM
Terminal 53, High Ref./Feedback = 1500 RPM
Switch S201 = OFF (U)
Speed RPM
P 6-15
Ref. voltage
P 6-11 10V
Illustration 1.9 Potentiometer Reference
12
+24V
18
Par. 5-10
27
Par. 5-12
29
Par. 5-13
32
Par. 5-14
37
39 42
50
53 54
55
1 k
11
1
1