Parameter Descriptions
5-33 Term X30/7 Digi Out (MCB 101)
Option:
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
3
3
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[84]
SL digital output E
[85]
SL digital output F
[120] Local ref active
[121] Remote ref active
[122] No alarm
[123] Start command activ
[124] Running reverse
[125] Drive in hand mode
[126] Drive in auto mode
[151] ATEX ETR cur. alarm
[152] ATEX ETR freq. alarm
[153] ATEX ETR cur. warning
[154] ATEX ETR freq. warning
[189] External Fan Control
[190] Safe Function active
[191] Safe Opt. Reset req.
[192] RS Flipflop 0
[193] RS Flipflop 1
[194] RS Flipflop 2
[195] RS Flipflop 3
[196] RS Flipflop 4
[197] RS Flipflop 5
[198] RS Flipflop 6
[199] RS Flipflop 7
90
®
VLT
AutomationDrive FC 301/302 Programming Guide
Function:
MG33MI02 - Rev. 2013-11-20
3.7.4 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option:
Function:
[0]
No operation
All digital and relay outputs are
default set to "No Operation".
[1]
Control Ready
The control card is ready. E.g.:
Feedback from a frequency converter
where the control is supplied by an
external 24 V (MCB 107) and the main
power to frequency converter is not
detected.
[2]
Drive ready
Frequency converter is ready to
operate. Mains and control supplies
are OK.
[3]
Drive rdy/rem ctrl
The frequency converter is ready for
operation and is in Auto On mode
[4]
Enable / no
Ready for operation. No start or stop
warning
commands have been applied (start/
disable). No warnings are active.
[5]
Running
Motor is running, and shaft torque
present.
[6]
Running / no
Output speed is higher than the
warning
speed set in 1-81 Min Speed for
Function at Stop [RPM] Min Speed for
Function at Stop [RPM]. The motor is
running and no warnings.
[7]
Run in range/no
Motor is running within the
warn
programmed current and speed
ranges set in parameter 4-50 Warning
Current Low and
parameter 4-53 Warning Speed High.
No warnings.
[8]
Run on ref/no
Motor runs at reference speed. No
warn
warnings.
[9]
Alarm
An alarm activates the output. No
warnings
[10]
Alarm or warning
An alarm or a warning activates the
output.
[11]
At torque limit
The torque limit set in
parameter 4-16 Torque Limit Motor
Mode or parameter 4-17 Torque Limit
Generator Mode has been exceeded.