Parameter Descriptions
Custom Readout (Value)
P 16-09
Custom Readout
Unit P 0-30
Max value
P 0-32
3
3
Min value
Linear
units only
P 0-31
0
Illustration 3.4 Custom Readout
The relation depends on the type of unit selected in
0-30 Custom Readout Unit:
Unit Type
Dimensionless
Speed
Flow, volume
Flow, mass
Velocity
Length
Temperature
Pressure
Power
Table 3.3 Speed Relations for Different Unit Types
0-30 Unit for User-defined Readout
Option:
[0]
None
*
[1]
%
[5]
PPM
[10]
1/min
[11]
rpm
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m³/s
[24]
m³/min
32
VLT
Motor Speed
High limit
P 4-13 (RPM)
P 4-14 (Hz)
Speed Relation
Linear
Quadratic
Cubic
Function:
It is possible to program a value to be shown in
the display of the LCP. The value has a linear,
squared or cubed relation to speed. This relation
depends on the unit selected (see Table 3.3). The
actual calculated value can be read in
parameter 16-09 Custom Readout, and/or shown in
the display be selecting [16-09] Custom Readout in
parameter 0-20 Display Line 1.1 Small to
0-24 Display Line 3 Large.
®
AutomationDrive FC 301/302 Programming Guide
0-30 Unit for User-defined Readout
Option:
[25]
m³/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
Motor Speed
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft³/s
[126] ft³/min
[127] ft³/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[160] °F
[170] psi
[171] lb/in²
[172] in WG
[173] ft WG
[180] HP
0-31 Min Value of User-defined Readout
Range:
0 CustomRea-
doutUnit
MG33MI02 - Rev. 2013-11-20
Function:
Function:
[ -999999.99 -
This parameter sets the min.
par. 0-32
value of the custom defined
*
CustomRea-
readout (occurs at zero speed).
doutUnit]
Only possible to set different
from 0 is when selecting a
linear unit in
parameter 0-30 Unit for User-
defined Readout. For Quadratic
and Cubic units the minimum
value will be 0.