Parameter Descriptions
3.2.6 0-5* Copy/Save
Copy parameters from and to the LCP. Use these
parameters for saving and copying set-ups from one
frequency converter to another.
3
3
0-50 LCP Copy
Option:
[0]
No copy
*
[1]
All to LCP
[2]
All from LCP
[3]
Size indep. from
LCP
[4]
File from MCO to
LCP
[5]
File from LCP to
MCO
[6]
Data from DYN to
LCP
[7]
Data from LCP to
DYN
[9]
Safety Par. from
LCP
[10] Delete LCP copy
data
0-51 Set-up Copy
Option:
[0] No copy
[1] Copy to set-
up 1
[2] Copy to set-
up 2
[3] Copy to set-
up 3
34
VLT
Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Copies all parameters in all set-ups
from the frequency converter memory
to the LCP memory.
Copies all parameters in all set-ups
from the LCP memory to the frequency
converter memory.
Copy only the parameters that are
independent of the motor size. The
latter selection can be used to
programme several frequency
converters with the same function
without disturbing motor data.
Use to delete the copy after the
transfer is complete.
Function:
No function
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 1.
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 2.
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 3.
®
AutomationDrive FC 301/302 Programming Guide
0-51 Set-up Copy
Option:
[4] Copy to set-
up 4
[9] Copy to all
3.2.7 0-6* Password
0-60 Main Menu Password
Range:
100
[-9999 -
*
9999 ]
0-61 Access to Main Menu w/o Password
Option:
[0]
Full access
*
[1]
LCP: Read
only
[2]
LCP: No
access
[3]
Bus: Read
only
[4]
Bus: No
access
[5]
All: Read only Read-only function for parameters on LCP,
[6]
All: No access No access from LCP, Fieldbus or FC standard
If [0] Full access is selected, parameter 0-60 Main Menu
Password, 0-65 Personal Menu Password and 0-66 Access to
Personal Menu w/o Password are ignored.
NOTICE
A more complex password protection is available for
OEMs upon request.
0-65 Quick Menu Password
Range:
200
[-9999 -
*
9999 ]
MG33MI02 - Rev. 2013-11-20
Function:
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 4.
Copies the parameters in the present set-up
over to each of the set-ups 1 to 4.
Function:
Define the password for access to the Main
Menu via the [Main Menu] key. If
0-61 Access to Main Menu w/o Password is
set to [0] Full access, this parameter will be
ignored.
Function:
Disables password defined in
parameter 0-60 Main Menu Password.
Prevent unauthorised editing of Main Menu
parameters.
Prevent unauthorised viewing and editing of
Main Menu parameters.
Read-only functions for parameters on
Fieldbus and/or FC standard bus.
No access to parameters is allowed via
Fieldbus and/or FC standard bus.
Fieldbus or FC standard bus.
bus is allowed.
Function:
Define the password for access to the Quick
Menu via the [Quick Menu] key. If
parameter 0-66 Access to Quick Menu w/o
Password is set to [0] Full access, this
parameter is ignored.