Parameter Descriptions
0-04 Operating State at Power-up (Hand)
Option:
[0]
Resume
3
3
[1]
Forced stop,
*
ref=old
[2]
Forced stop,
ref=0
3.2.2 0-1* Set-up Operations
Define and control the individual parameter set-ups.
The frequency converter has 4 parameter set-ups that can
be programmed independently of each other. This makes
the frequency converter very flexible and able to solve
advanced control functionality problems, often saving the
cost of external control equipment. For example these can
be used to program the frequency converter to operate
according to one control scheme in one set-up (e.g. motor
1 for horizontal movement) and another control scheme in
another set-up (e.g. motor 2 for vertical movement).
Alternatively they can be used by an OEM machine builder
to identically program all their factory fitted frequency
converters for different machine types within a range to
have the same parameters and then during production/
commissioning simply select a specific set-up depending
on which machine the frequency converter is installed on.
The active set-up (i.e. the set-up in which the frequency
converter is currently operating) can be selected in
parameter 0-10 Active Set-up and is displayed in the LCP.
Using Multi set-up it is possible to switch between set-ups
with the frequency converter running or stopped, via
digital input or serial communication commands. If it is
necessary to change set-ups whilst running, ensure
parameter 0-12 This Set-up Linked to is programmed as
required. Using parameter 0-11 Edit Set-up it is possible to
edit parameters within any of the set-ups whilst continuing
the frequency converter operation in its active set-up
which can be a different set-up to that being edited. Using
parameter 0-51 Set-up Copy it is possible to copy parameter
settings between the set-ups to enable quicker commis-
sioning if similar parameter settings are required in
different set-ups.
0-10 Active Set-up
Option:
[0]
Factory
setup
26
VLT
Function:
Restarts the frequency converter, maintaining
the same and the same start/stop settings
(applied by [Hand On/Off]) as before the
frequency converter was powered down.
Restarts the frequency converter with a saved
local reference, after mains voltage reappears
and after pressing [Hand On].
Resets the local reference to 0 upon
restarting the frequency converter.
Function:
Select the set-up to control the frequency
converter functions.
Cannot be changed. It contains the Danfoss
data set, and can be used as a data source
when returning the other set-ups to a known
state.
®
AutomationDrive FC 301/302 Programming Guide
0-10 Active Set-up
Option:
[1]
Set-up 1
*
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Multi Set-
up
Use parameter 0-51 Set-up Copy to copy a set-up to one or
all other set-ups. Stop the frequency converter before
switching between set-ups where parameters marked 'not
changeable during operation' have different values. To
avoid conflicting settings of the same parameter within 2
different set-ups, link the set-ups together using
parameter 0-12 This Set-up Linked to. Parameters which are
'not changeable during operation' are marked FALSE in the
parameter lists in chapter 4 Parameter Lists.
0-11 Edit Set-up
Option:
[0]
Factory
setup
[1]
Set-up 1
*
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Active Set-
up
MG33MI02 - Rev. 2013-11-20
Function:
[1] Set-up 1 to [4] Set-up 4 are the 4 separate
parameter set-ups within which all parameters
can be programmed.
Remote selection of set-ups using digital
inputs and the serial communication port. This
set-up uses the settings from
parameter 0-12 This Set-up Linked to. Stop the
frequency converter before making changes to
open- and closed loop functions
Function:
Select the set-up to be edited (i.e.
programmed) during operation; either the
active set-up or one of the inactive set-ups.
Cannot be edited but it is useful as a data
source to return the other set-ups to a known
state.
[1] Set-up 1 to [4] Set-up 4 can be edited
freely during operation, independently of the
active set-up.
Can also be edited during operation. Edit the
selected set-up from a range of sources: LCP,
FC RS-485, FC USB or up to 5 fieldbus sites.