Troubleshooting
ALARM 46, Power card supply
The supply on the power card is out of range.
There are 3 power supplies generated by the switch mode
power supply (SMPS) on the power card: 24 V, 5 V, ±18 V.
When powered with 24 V DC with the MCB 107 option,
only the 24 V and 5 V supplies are monitored. When
powered with 3-phase mains voltage, all 3 supplies are
monitored.
Troubleshooting
Check for a defective power card.
Check for a defective control card.
5
5
Check for a defective option card.
If a 24 V DC power supply is used, verify proper
supply power.
WARNING 47, 24 V supply low
The 24 V DC is measured on the control card. This alarm
arises when the detected voltage of terminal 12 is lower
than 18 V.
Troubleshooting
Check for a defective control card.
WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of
allowable limits. The power supply is measured on the
control card. Check for a defective control card. If an
option card is present, check for an overvoltage condition.
WARNING 49, Speed limit
When the speed is not within the specified range in
4-11 Motor Speed Low Limit [RPM] and 4-13 Motor Speed
High Limit [RPM], the frequency converter shows a warning.
When the speed is below the specified limit in 1-86 Trip
Speed Low [RPM] (except when starting or stopping), the
frequency converter trips.
ALARM 50, AMA calibration failed
Contact Danfoss supplier or Danfoss service department.
ALARM 51, AMA check U
The settings for motor voltage, motor current and motor
power are wrong. Check the settings in parameters 1-20 to
1-25.
ALARM 52, AMA low I
The motor current is too low. Check the settings.
ALARM 53, AMA motor too big
The motor is too big for the AMA to operate.
ALARM 54, AMA motor too small
The motor is too small for the AMA to operate.
ALARM 55, AMA parameter out of range
The parameter values of the motor are outside of the
acceptable range. AMA cannot run.
ALARM 56, AMA interrupted by user
The user has interrupted the AMA.
220
®
VLT
AutomationDrive FC 301/302 Programming Guide
and I
nom
nom
nom
MG33MI02 - Rev. 2013-11-20
ALARM 57, AMA internal fault
Try to restart AMA again. Repeated restarts can over heat
the motor.
ALARM 58, AMA Internal fault
Contact the Danfoss supplier.
WARNING 59, Current limit
The current is higher than the value in 4-18 Current Limit.
Ensure that motor data in parameters 1–20 to 1–25 are set
correctly. Possibly increase the current limit. Be sure that
the system can operate safely at a higher limit.
WARNING 60, External interlock
A digital input signal is indicating a fault condition external
to the frequency converter. An external interlock has
commanded the frequency converter to trip. Clear the
external fault condition. To resume normal operation,
apply 24 V DC to the terminal programmed for external
interlock. Reset the frequency converter.
WARNING/ALARM 61, Feedback error
An error between calculated speed and speed
measurement from feedback device. The function Warning/
Alarm/Disabling setting is in parameter 4-30 Motor
Feedback Loss Function. Accepted error setting in
parameter 4-31 Motor Feedback Speed Error and the allowed
time the error occur setting in parameter 4-32 Motor
Feedback Loss Timeout. During a commissioning procedure
the function may be effective.
WARNING 62, Output frequency at maximum limit
The output frequency has reached the value set in
4-19 Max Output Frequency. Check the application to
determine the cause. Possibly increase the output
frequency limit. Be sure the system can operate safely at a
higher output frequency. The warning clears when the
output drops below the maximum limit.
ALARM 63, Mechanical brake low
The actual motor current has not exceeded the "release
brake" current within the "start delay" time window.
WARNING 64, Voltage limit
The combination of load and speed demands a motor
voltage higher than the actual DC link voltage.
WARNING/ALARM 65, Control card over temperature
The cut-out temperature of the control card is 80 °C.
Troubleshooting
Check that the ambient operating temperature is
within limits
Check for clogged filters
Check fan operation
Check the control card
WARNING 66, Heat sink temperature low
The frequency converter is too cold to operate. This
warning is based on the temperature sensor in the IGBT
module.