Parameter Description
0-42 [Auto on] Key on LCP
Option:
Function:
[0] Disabled
Key disabled avoids accidental usage of the key.
[1] Enabled
[Auto On] key is enabled
[2] Password Avoid unauthorized start in Auto mode. If
parameter 0-42 [Auto on] Key on LCP is included in
the My Personal Menu, then define the password
in parameter 0-65 Personal Menu Password.
Otherwise define the password in
parameter 0-60 Main Menu Password.
0-43 [Reset] Key on LCP
Option:
Function:
[0] Disabled
Key disabled avoids accidental usage of the
key.
[1] Enabled
[Reset] key is enabled
[2] Password
Avoid unauthorized resetting. If
parameter 0-43 [Reset] Key on LCP is included
in the 0-25 My Personal Menu, then define the
password in parameter 0-65 Personal Menu
Password. Otherwise define the password in
parameter 0-60 Main Menu Password.
[3] Enabled
without OFF
[4] Password
without OFF
[5] Enabled with
Pressing the key resets the frequency
OFF
converter but does not start it.
[6] Password
Prevents unauthorized reset. Upon authorized
with OFF
reset, the frequency converter does not start.
See option [2] Password for information on
how to set the password.
0-44 [Off/Reset] Key on LCP
Option:
Function:
[0] Disabled
Key disabled avoids accidental usage of the key.
[1] Enabled
[2] Password
0-45 [Drive Bypass] Key on LCP
Press [Off] and select [0] Disabled to avoid accidental stop of the
frequency converter. Press [Off] and select [2] Password to avoid
unauthorised bypass of the frequency converter. If 0-45 [Drive
Bypass] Key on LCP is included in the Quick Menu, then define
the password in parameter 0-65 Personal Menu Password.
Option:
[0]
Disabled
[1]
Enabled
[2]
Password
MG20O702
Programming Guide
3.2.6 0-5* Copy/Save
Copy parameters from and to the LCP. Use these
parameters for saving and copying set-ups from one
frequency converter to another.
0-50 LCP Copy
Option:
[0] No copy
[1] All to LCP
[2] All from
[3] Size indep.
0-51 Set-up Copy
Option:
[0] No copy
[1] Copy to
[2] Copy to
[3] Copy to
[4] Copy to
[9] Copy to
Function:
Key disabled avoids
accidental usage of the
key.
Danfoss A/S © Rev. 2014-01-21 All rights reserved.
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
No function
Copies all parameters in all set-ups from the
frequency converter memory to the LCP
memory. For service purposes it is recommended
to copy all parameters to the LCP after commis-
sioning.
Copies all parameters in all set-ups from the LCP
LCP
memory to the frequency converter memory.
Copies only the parameters that are independent
from LCP
of the motor size. The latter selection can be
used to programme several frequency converters
with the same function without disturbing motor
data which are already set.
Function:
No function
Copies all parameters in the present
set-up 1
Programming Set-up (defined in
parameter 0-11 Programming Set-up) to Set-up 1.
Copies all parameters in the present
set-up 2
Programming Set-up (defined in
parameter 0-11 Programming Set-up) to Set-up 2.
Copies all parameters in the present
set-up 3
Programming Set-up (defined in
parameter 0-11 Programming Set-up) to Set-up 3.
Copies all parameters in the present
set-up 4
Programming Set-up (defined in
parameter 0-11 Programming Set-up) to Set-up 4.
Copies the parameters in the present set-up over
all
to each of the set-ups 1 to 4.
3
3