Parameter Description
13-52 SL Controller Action
Array [20]
Option:
Function:
[28] Freeze output
Freezes the output frequency of the
frequency converter.
[29] Start timer 0
Starts timer 0, see parameter 13-20 SL
Controller Timer for further description.
[30] Start timer 1
Starts timer 1, see parameter 13-20 SL
Controller Timer for further description.
[31] Start timer 2
Starts timer 2, see parameter 13-20 SL
Controller Timer for further description.
[32] Set digital out
Any output with 'digital output 1' selected
A low
is low (off).
[33] Set digital out
Any output with 'digital output 2' selected
B low
is low (off).
[34] Set digital out
Any output with 'digital output 3' selected
C low
is low (off).
[35] Set digital out
Any output with 'digital output 4' selected
D low
is low (off).
[36] Set digital out
Any output with 'digital output 5' selected
E low
is low (off).
[37] Set digital out
Any output with 'digital output 6' selected
F low
is low (off).
[38] Set digital out
Any output with 'digital output 1' selected
A high
is high (closed).
[39] Set digital out
Any output with 'digital output 2' selected
B high
is high (closed).
[40] Set digital out
Any output with 'digital output 3' selected
C high
is high (closed).
[41] Set digital out
Any output with 'digital output 4' selected
D high
is high (closed).
[42] Set digital out
Any output with 'digital output 5' selected
E high
is high (closed).
[43] Set digital out
Any output with 'digital output 6' selected
F high
is high (closed).
[60] Reset Counter
Resets Counter A to zero.
A
[61] Reset Counter
Resets Counter A to zero.
B
[70] Start Timer 3
Starts timer 3, see parameter 13-20 SL
Controller Timer for further description.
[71] Start Timer 4
Starts timer 4, see parameter 13-20 SL
Controller Timer for further description.
[72] Start Timer 5
Starts timer 5, see parameter 13-20 SL
Controller Timer for further description.
[73] Start Timer 6
Starts timer 6, see parameter 13-20 SL
Controller Timer for further description.
MG20O702
Programming Guide
13-52 SL Controller Action
Array [20]
Option:
[74] Start Timer 7
[80] Sleep Mode
[81] Derag
Danfoss A/S © Rev. 2014-01-21 All rights reserved.
Function:
Starts timer 7, see parameter 13-20 SL
Controller Timer for further description.
Starts the Sleep Mode.
Starts Deragging (see parameter groups
29-1* Deragging Function to 29-3* for
further information)
3
3
111