Parameter Description
31-01 Bypass Start Time Delay
Range:
Function:
30 s
[0 - 60 s] Set the time delay within the time when the
*
bypass receives a run command and the time
when it starts the motor at full speed. A
countdown timer will display time left.
31-02 Bypass Trip Time Delay
Range:
Function:
0 s
[0 - 300
Set the time delay within the time that the drive
*
s]
experiences an alarm that stops it and the time
when the motor is automatically switched to
bypass control. If the time delay is set to zero, a
drive alarm will not automatically switch the
motor to bypass control.
31-03 Test Mode Activation
Option:
Function:
[0] Disabled [0] Disabled means that the Test Mode is disabled.
[1] Enabled [1] Enabled means that the motor runs in bypass,
while the frequency converter can be tested in an
open circuit. In this mode the LCP will not control
start/stop of the bypass.
31-10 Bypass Status Word
Range:
Function:
0
[0 - 65535 ] Views the status of the bypass as a
*
hexadecimal value.
31-11 Bypass Running Hours
Range:
Function:
0 h
[0 -
Views the number of hours in which the
*
2147483647 h]
motor has run in Bypass Mode. The
counter can be reset in
parameter 15-07 Reset Running Hours
Counter. The value is saved, when the
frequency converter is turned off.
31-19 Remote Bypass Activation
Option:
Function:
[0]
Disabled
[1]
Enabled
Feature: Unknown.