5.5

SLSV, SLSV_R SIMOLINK send block for one setpoint

Symbol
Hardware addresse SLB ―GV
Address of the first slave ―I
Number of slaves ―I
Channel number for the setpoint ―I
Setpoint at slave 0 ―DI
Setpoint at slave 1 ―DI
Setpoint at slave 2 ―DI
Setpoint at slave 3 ―DI
Setpoint at slave 4 ―DI
Setpoint at slave 5 ―DI
Setpoint at slave 6 ―DI
Setpoint at slave 7 ―DI
Brief description
Mode of operation
Function Blocks - FM 458-1 DP
Edition 12.2004
SLSV
TAD
FSL
NSL
CSV
XS0
XS1
XS2
XS3
XS4
XS5
XS6
XS7
A maximum of 8 setpoints can be transferred to a maximum of 8 slaves
using the SLSV send block. Only one setpoint can be sent to each slave,
and for all of the slaves, only the same channel number can be
addressed.
The SLSV and SLSV_R function blocks are functionally identical. The
only difference is the data type of the setpoint connections XS0 to XS7:
SLSV:
SLSV_R:
1. The SLSV send block executes the following steps while the system is
being initialized:
− Checks the task assignment
− Initializes the task-list of the SLB module corresponding to the data
configured at the inputs
2. In the normal system mode ("RUN" mode), the SLSV send block
executes the following:
− Calculates the setpoints
− Checks that the inputs are within the permissible value ranges
− Enters the setpoints to be sent into the write buffer of the SLB
module
SIMOLINK drive coupling
SEQ
I ― Sequence numbedr
YF
I ― Block error status
QF
BO ― Group error bit
DINT
REAL