Maximum Position; On Target Window; On Target Time; Preset Reference - Danfoss VLT AutomationDrive FC 302 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Parameter Descriptions

3-07 Maximum Position

Range:
100000
CustomRea-
[-2147483648
doutUnit2
- 2147483647
*
CustomRea-
doutUnit2]

3-08 On Target Window

Range:
5 CustomRea-
[0 -
doutUnit2
2147483647
*
CustomRea-
doutUnit2]
MG33MP02
Programming Guide
Function:
NOTICE
This parameter is only
available with software
version 48.XX.
Enter the maximum position. This
parameter defines the position
range in linear and axis modes
(parameter 17-76 Position Axis
Mode).
Position range limits:
Linear:
Parameter 3-06 Minimum
Position to
parameter 3-07 Maximum
Position.
Rotary: 0–
parameter 3-07 Maximum
Position.
The position limit function uses
this parameter
(parameter 4-73 Position Limit
Function).
Function:
NOTICE
This parameter is only
available with software
version 48.XX.
The frequency converter
considers the positioning
completed and sends the on
target signal when the actual
position is within
parameter 3-08 On Target
Window for the duration of
parameter 3-09 On Target Time
and the actual speed is less
than parameter 3-05 On
Reference Window.
Danfoss A/S © 10/2018 All rights reserved.

3-09 On Target Time

Range:
Function:
NOTICE
1 ms
[0 - 60000
*
ms]
This parameter is only available with
software version 48.XX.
Enter the time for evaluating the on
target window, see also parameter 3-08 On
Target Window.
3.4.2 3-1* References
Select the preset references. Select Preset ref. bit 0/1/2 [16],
[17], or [18] for the corresponding digital inputs in
parameter group 5-1* Digital Inputs.

3-10 Preset Reference

Array [8]
Range: 0-7
Range:
Function:
0 %
[-100 -
Enter up to 8 different preset references (0–7) in
*
100 %]
this parameter, using array programming. The
preset reference is stated as a percentage of the
value Ref
(parameter 3-03 Maximum Reference).
MAX
If a Ref
different from 0
MIN
(parameter 3-02 Minimum Reference) is
programmed, the preset reference is calculated
as a percentage of the full reference range, that
is on the basis of the difference between Ref
and Ref
. Afterwards, the value is added to
MIN
Ref
. When using preset references, select
MIN
preset reference bit 0/1/2 [16], [17] or [18] for the
corresponding digital inputs in parameter group
5-1* Digital Inputs.
12 (+24V)
Preset
76543210
29
10101010
[P 5-13=Preset ref. bit 0]
11001100
32
[P 5-14=Preset ref. bit 1]
33
11110000
[P 5-15=Preset ref. bit 2]
Illustration 3.21 Preset Reference
3
3
MAX
77