Parameter Descriptions
1-82 Min Speed for Function at Stop [Hz]
Range:
Function:
Size related
[ 0 - 500.0
Set the output frequency at which
*
Hz]
to activate parameter 1-80 Function
at Stop.

1-83 Precise Stop Function

Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
Valid for FC 302 only.
[0]
Precise
Only optimal when the operational speed, for
ramp
example the operational speed of a conveyor belt,
*
stop
is constant. This is an open-loop control. Achieves
high repetitive precision at the stop point.
[1]
Cnt stop
Counts the number of pulses, typically from an
with
encoder, and generates a stop signal after a pre-
reset
programmed number of pulses, defined in
parameter 1-84 Precise Stop Counter Value, has
been received at terminal 29 or terminal 33.
This is direct feedback with one-way closed-loop
control.
The counter function is activated (starts timing) at
the edge of the start signal (when it changes from
stop to start). After each precise stop, the number
of pulses counted during ramp down to 0 RPM is
reset.
[2]
Cnt stop
Same as [2] Cnt stop with reset but the number of
w/o
pulses counted during ramp down to 0 RPM is
reset
deducted from the counter value entered in
parameter 1-84 Precise Stop Counter Value.
This reset function can be used to compensate for
the extra distance done during ramping down
and to reduce the impacts of gradual wear of
mechanical parts.
[3]
Speed
Stops at precisely the same point, regardless of
comp
the present speed. The stop signal is delayed
stop
internally when the present speed is lower than
the maximum speed (set in parameter 4-19 Max
Output Frequency).
The delay is calculated on the basis of the
reference speed of the frequency converter and
not on the basis of the actual speed. Make sure
that the frequency converter has ramped up
before activating the speed compensated stop.
[4]
Com cnt
Same as Speed comp stop but after each precise
stop
stop, the number of pulses counted during ramp
w/rst
down to 0 RPM is reset.
[5]
Comp
Same as Speed comp stop but the number of
cnt stop
pulses counted during ramp down to 0 RPM is
w/o r
deducted from the counter value entered in
parameter 1-84 Precise Stop Counter Value.
MG33MP02
Programming Guide
1-83 Precise Stop Function
Option:
The precise stop functions are advantageous in
applications where high precision is required.
If using a standard stop command, the accuracy is
determined by the internal task time. That is not the case
when using the precise stop function. It eliminates the task
time dependence and increases the accuracy substantially.
The frequency converter tolerance is normally given by its
task time. However, by using its special precise stop
function, the tolerance is independent of the task time
because the stop signal immediately interrupts the
execution of the frequency converter program. The precise
stop function gives a highly reproducible delay from the
stop signal is given until the ramping down starts. Run a
test to find this delay as it is a sum of sensor, PLC,
frequency converter, and mechanical parts.
To ensure optimum accuracy, there should be at least 10
cycles during ramping down, see:
The precise stop function is set up here and enabled from
DI at terminal 29 or terminal 33.

1-84 Precise Stop Counter Value

Range:
100000
*

1-85 Precise Stop Speed Compensation Delay

Range:
10 ms
*
Danfoss A/S © 10/2018 All rights reserved.
Function:
This reset function can be used to compensate for
the extra distance done during ramping down
and to reduce the impacts of gradual wear of
mechanical parts.
Parameter 3-42 Ramp 1 Ramp Down Time.
Parameter 3-52 Ramp 2 Ramp Down Time.
Parameter 3-62 Ramp 3 Ramp down Time.
Parameter 3-72 Ramp 4 Ramp Down Time.
Function:
[0 -
Enter the counter value to be used in
999999999 ]
the integrated precise stop function,
parameter 1-83 Precise Stop Function.
The maximum permissible frequency at
terminal 29 or 33 is 110 kHz.
NOTICE
Not used for selections [0] Precise
ramp stop and [3] Speed comp stop
in parameter 1-83 Precise Stop
Function.
Function:
[0 -
Enter the delay time for sensors, PLCs, and so
100 ms]
on for use in parameter 1-83 Precise Stop
Function. In speed compensated stop mode,
the delay time at different frequencies has a
major influence on the stop function.
3