VLT® Decentral Drive FCD 302
Operating Guide
7.7.2 Recommended Maximum Pre-fuse Size 25 A
Table 21: FCD 302 Pre-fuses Meeting UL/cUL Requirements
Brand
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
SIBA
Little Fuse
Ferraz-Shawmut
Ferraz-Shawmut
Ferraz-Shawmut
5 A (0.37 kW (0.5 hp)), 7 A (0.55 kW (0.75 hp)), 9 A (0.75 kW (1.0 hp)), 12 A (1.1 kW (1.5 hp)), 15 A (1.5 kW (2.0 hp)), 20 A (2.2 kW (3.0 hp)), 25 A (3 kW
1
(4.0 hp))
Table 22: FCD 302 DC Voltage Level
DC voltage level
Inverter undervoltage disable
Undervoltage warning
Inverter undervoltage re-enable (warning reset)
Overvoltage warning (without brake)
Dynamic brake turn on
Inverter overvoltage re-enable (warning reset)
Overvoltage warning (with brake)
Overvoltage trip
66 | Danfoss A/S © | 2020.07
Fuse type
UL file number
(1)
FWH-
E91958
KTS-R
E4273
JKS-
E4273
JJS-
E4273
FNQ-R-
E4273
KTK-R-
E4273
LP-CC-
E4273
5017906-
E180276
KLS-R
E81895
ATM-R
E2137
A6K-R
E2137
HSJ
E2137
Specifications
UL category (CCN code)
JFHR2
RK1/JDDZ
J/JDDZ
T/JDDZ
CC/JDDZ
CC/JDDZ
CC/JDDZ
RK1/JDDZ
RK1/JDDZ
CC/JDDZ
RK1/JDDZ
J/HSJ
380–480 V units (V DC)
373
410
398
778
778
795
810
820
AQ267036816112EN-000101 / 130R0208
Need help?
Do you have a question about the VLT Decentral Drive FCD 302 and is the answer not in the manual?
Questions and answers