Parameter Descriptions

5-59 Pulse Filter Time Constant #33

Range:
100
[1 - 1000
ms
ms]
*
3
3

3.6.6 5-6* Pulse Outputs

NOTICE
These parameters cannot be adjusted while the motor is
running.
These parameters configure pulse outputs with their
functions and scaling. Terminals 27 and 29 are allocated to
pulse output via parameter 5-01 Terminal 27 Mode and
parameter 5-02 Terminal 29 Mode, respectively.
Output value
High output
value
P 5-60(term27)
P 5-63(term29)
Illustration 3.40 Configuration of Pulse Outputs
Options for readout output variables:
[0]
No operation
[45]
Bus control
[48]
Bus control
timeout
[51]
MCO-controlled
130
®
VLT
AutomationDrive FC 301/302
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the pulse filter time constant. The
low-pass filter reduces the influence and
dampens oscillations on the feedback
signal from the control.
This is an advantage if there is a lot of
noise in the system.
High freq.
Output
P 5-62(term27)
(Hz)
P 5-65(term29)
Parameters for configuring the scaling
and output functions of pulse outputs.
The pulse outputs are designated to
terminals 27 or 29. Select terminal 27
output in parameter 5-01 Terminal 27
Mode and terminal 29 output in
parameter 5-02 Terminal 29 Mode.
Danfoss A/S © 10/2018 All rights reserved.
NOTICE
[97]
Reference After
Ramp
This option is available only with
software version 48.XX.
Actual speed reference after the ramp.
Use this output as master signal for
speed synchronization of follower
frequency converters. The reference is set
in parameter 16-48 Speed Ref. After Ramp
[RPM].
NOTICE
[99]
Virtual Master
Speed
This option is available only with
software version 48.XX.
Virtual master signal for controlling the
speed or position of the followers.
[100] Output
frequency
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque relative
to limit
[105] Torque relative
to rated
[106] Power
[107] Speed
[108] Torque
[109] Max. out freq
5-60 Terminal 27 Pulse Output Variable
Option:
Function:
[0]
No operation
Select the display output for terminal
27.
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[51]
MCO controlled
NOTICE
[97]
Reference After
Ramp
This option is available only with
software version 48.XX.
Actual speed reference after the ramp.
Use this output as master signal for
speed synchronization of follower
frequency converters. The reference is
set in parameter 16-48 Speed Ref. After
Ramp [RPM].
NOTICE
[99]
Virtual Master
Speed
This option is available only with
software version 48.XX.
Virtual master signal for controlling
the speed or position of the followers.
[100] Output frequency
[101] Reference