Parameter Descriptions
1-72 Start Function
Option:
Function:
[0]
DC Hold/
Energizes motor with a DC hold current
delay time
(parameter 2-00 DC Hold Current) during the
start delay time.
[1]
DC Brake/
Energizes motor with a DC brake current
delay time
(parameter 2-01 DC Brake Current) during the
start delay time.
[2]
Coast/delay
Motor coasted during the start delay time
time
(inverter off).
*
[3]
Start speed
Only possible with VVC
cw
Connect the function described in
parameter 1-74 Start Speed [RPM] and
parameter 1-76 Start Current in the start delay
time.
Regardless of the value applied by the
reference signal, the output speed applies the
setting of the start speed in
parameter 1-74 Start Speed [RPM] or
parameter 1-75 Start Speed [Hz], and the
output current corresponds to the setting of
the start current in parameter 1-76 Start
Current. This function is typically used in
hoisting applications without counterweight
and especially in applications with a cone-
motor where the start is clockwise, followed
by rotation in the reference direction.
[4]
Horizontal
Only possible with VVC
operation
For obtaining the function described in
parameter 1-74 Start Speed [RPM] and
parameter 1-76 Start Current during the start
delay time. The motor rotates in the reference
direction. If the reference signal equals 0,
parameter 1-74 Start Speed [RPM] is ignored
and the output speed equals 0. The output
current corresponds to the setting of the start
current in parameter 1-76 Start Current.
[5]
VVC+/Flux
For the function described in
clockwise
parameter 1-74 Start Speed [RPM] only. The
start current is calculated automatically. This
function uses the start speed in the start delay
time only. Regardless of the value set by the
reference signal, the output speed equals the
setting of the start speed in
parameter 1-74 Start Speed [RPM]. [3] Start
speed/current clockwise and [5] VVC
clockwise are typically used in hoisting
applications. [4] Start speed/current in reference
direction is particularly used in applications
with counterweight and horizontal movement.
[6]
Hoist Mech.
For utilizing mechanical brake control
Brake Rel
functions (parameter 2-24 Stop Delay to
parameter 2-28 Gain Boost Factor). This
MG33MP02
Programming Guide
1-72 Start Function
Option:
[7]

1-73 Flying Start

Option:
+
.
+
.
[0] Disabled
[1] Enabled
[2] Enabled
[3] Enabled
[4] Enab.
NOTICE
This function is not recommended for hoisting
applications.
For power levels above 55 kW, flux mode must be used
to achieve the best performance.
+
/Flux
NOTICE
To obtain the best flying start performance, the
advanced motor data, parameter 1-30 Stator Resistance
(Rs) to parameter 1-35 Main Reactance (Xh), must be
correct.
Danfoss A/S © 10/2018 All rights reserved.
Function:
parameter is only active in flux control
principle, in a mode with motor feedback or
sensorless mode.
VVC+/Flux
counter-cw
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
This function makes it possible to catch a freely
spinning motor, for exmaple coasted because of
mains dropout.
When Flying start is enabled,
parameter 1-71 Start Delay and
parameter 1-72 Start Function have no function.
When options [1] and [2] are enabled,
parameter 1-58 Flying Start Test Pulses Current
and parameter 1-59 Flying Start Test Pulses
Frequency are used to specify conditions for
flying start.
Options [3] and [4] are set to search for the
motor in the reference direction only, which
allows a faster execution of the motor catch.
No function.
Enable after coast.
Enable at every start.
Always
Enable after coast, search in reference direction
Ref. Dir.
only.
Enable at every start, search in reference
Always Ref.
direction only.
Dir.
3
3
59