Parameter Descriptions
3-15 Reference Resource 1
Option:
Function:
Select the speed reference source in
parameter 3-15 when
parameter 1-00 Configuration Mode is set
to [9] in positioning mode.
NOTICE
The options 3, 4, 5, 6, 12, 13, 14 are
only available with software version
48.XX
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
[3]
24V encoder
32/33
[4]
MCB 102
[5]
MCB 103
[6]
Virtual Master
[7]
Frequency input
29
[8]
Frequency input
33
[11] Local bus
Reference from terminals 68 and 69.
reference
[12] Preset Reference Select this option to set the speed
reference in parameter 3-10 Preset
Reference together with the preset target
in parameter 3-20 Preset Target to calculate
speed profile for positioning.
[13] 24V encoder
27/29
[14] MCB 102
Absolute
[20] Digital
pot.meter
[21] Analog input
®
VLT
General Purpose I/O MCB 101
X30/11
[22] Analog input
®
VLT
General Purpose I/O MCB 101
X30/12
[29] Analog Input
X48/2
3-16 Reference Resource 2
Option:
Function:
NOTICE
The options 3, 4, 5, 6, 12, 13, and 14
are only available for software version
48.XX.
Select the reference input to be used for the
2
nd
reference signal. Parameter 3-15 Reference
Resource 1, parameter 3-16 Reference Resource
2, and parameter 3-17 Reference Resource 3
MG33MP02
Programming Guide
3-16 Reference Resource 2
Option:
[0]
No function
[1]
Analog Input
53
[2]
Analog Input
54
[3]
24V encoder
32/33
[4]
MCB 102
[5]
MCB 103
[6]
Virtual Master Master signal for the drive which hosts the
[7]
Frequency
input 29
[8]
Frequency
input 33
[11] Local bus
reference
[12] Preset
Reference
[13] 24V encoder
27/29
[14] MCB 102
Absolute
Danfoss A/S © 10/2018 All rights reserved.
Function:
define up to 3 different reference signals.
The sum of these reference signals defines
the actual reference.
Whenparameter 1-00 Configuration Mode is
set to[10] for synchronizing mode, configure
parameter 3-16 to select the source for
master position.
When parameter 1-00 Configuration Mode is
set to[9] for positioning mode, configure
parameter 3-16 to select the source for
target position.
Single signal generated from 24V High
Threshold Logic (HTL) encoder connected to
terminals 32 and 33. Configure the 24V
encoder interface in Parameter group 5.7*
24V Encoder Option.
Program terminals 32/33 to [0] No operation.
®
This is only available for VLT
Encoder
Option MCB 102. Configure the encoder
interface in parameter groups 17-0*, 17-1*
and 17-2*.
®
This is only available for VLT
Resolver
Option MCB 103. Configure the resolver
interface in parameter groups 17-5*.
virtual master without an external
connection.
Reference from terminals 68 and 69.
Single signal generated from 24V High
Threshold Logic (HTL) encoder connected to
terminals 27 and 29. Configure the 24V
encoder interface in parameter group 5.7*
24V Encoder Input.
Program terminals 27/29 to [0] No operation.
The option is only available for VLT
Option MCB 102 with version 4.00 and
newer and when parameter 17-00 Encoders
Connected is set to option[1] Two Encoders.
3
3
®
Encoder
79