Parameter Descriptions

0-04 Operating State at Power-up (Hand)

Option:
Function:
Select the operating mode upon
reconnection of the frequency converter to
mains voltage after power down in hand-on
mode.
[0]
Resume
Restart the frequency converter, maintaining
the start/stop settings (applied by [Hand On/
Off]) selected before the power-down of the
frequency converter.
[1]
Forced stop,
Restart the frequency converter with a saved
*
ref=old
local reference after mains voltage reappears
and after pressing [Hand On].
[2]
Forced stop,
Reset the local reference to 0 upon restarting
ref=0
the frequency converter.

3.1.2 0-1* Set-up Operations

Define and control the individual parameter set-ups.
The frequency converter has 4 parameter set-ups that can
be programmed independently of each other. This makes
the frequency converter very flexible and able to solve
advanced control functionality problems, often saving the
cost of external control equipment. Parameter set-ups can
be used to program the frequency converter to operate
according to 1 control scheme in 1 set-up (for example
motor 1 for horizontal movement) and another control
scheme in another set-up (for example motor 2 for vertical
movement). Alternatively, parameter set-ups can be used
by an OEM machine builder to identically program all their
factory-fitted frequency converters for different machine
types within a range to have the same parameters. During
production/commissioning, simply select a specific set-up
depending on which machine the frequency converter is
installed on.
The active set-up (that is the set-up in which the frequency
converter is currently operating) can be selected in
parameter 0-10 Active Set-up and is shown in the LCP. By
using multi set-up, it is possible to switch between set-ups
with the frequency converter running, or it can be stopped
via digital input or serial communication commands. If it is
necessary to change set-ups while the frequency converter
is running, ensure that parameter 0-12 This Set-up Linked to
is programmed as required. By using parameter 0-11 Edit
Set-up, it is possible to edit parameters within any of the
set-ups while continuing the operation of the frequency
converter in its active set-up, which can be a different set-
up to the one being edited. By using parameter 0-51 Set-up
Copy, it is possible to copy parameter settings between the
set-ups to enable quicker commissioning if similar
parameter settings are required in different set-ups.
MG33MP02
Programming Guide

0-10 Active Set-up

Option:
[0]
Factory
setup
[1]
Set-up 1
*
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Multi Set-
up
Use parameter 0-51 Set-up Copy to copy a set-up to 1 or all
other set-ups. Stop the frequency converter before
switching between set-ups where parameters marked not
changeable during operation have different values. To avoid
conflicting settings of the same parameter within 2
different set-ups, link the set-ups together using
parameter 0-12 This Set-up Linked to. Parameters which are
not changeable during operation are marked FALSE in the
parameter lists in chapter 5 Parameter Lists.

0-11 Edit Set-up

Option:
[0]
Factory
setup
[1]
Set-up 1
*
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Active Set-
up
Danfoss A/S © 10/2018 All rights reserved.
Function:
Select the set-up to control the frequency
converter functions.
Cannot be changed. It contains the Danfoss
data set and can be used as a data source
when returning the other set-ups to a known
state.
[1] Set-up 1 to [4] Set-up 4 are the 4 separate
parameter set-ups within which all parameters
can be programmed.
Remote set-up selections using digital inputs
and the serial communication port. This set-up
uses the settings from parameter 0-12 This Set-
up Linked to. Stop the frequency converter
before making changes to open and closed-
loop functions.
Function:
Select the set-up to be edited (that is
programmed) during operation; either the
active set-up or 1 of the inactive set-ups.
Cannot be edited but it is useful as a data
source to return the other set-ups to a known
state.
[1] Set-up 1 to [4] Set-up 4 can be edited freely
during operation, independently of the active
set-up.
Can also be edited during operation. Edit the
selected set-up from a range of sources: LCP,
FC RS485, FC USB, or up to 5 fieldbus sites.
3
3
25