Parameter Descriptions

3.15.7 15-2* Historic Log

View up to 50 logged data items via the array parameters
in this parameter group. Data is logged every time an
event occurs (not to be confused with SLC events). Events
3
3
in this context are defined as a change in 1 of the
following areas:
Digital inputs.
Digital outputs.
Warning word.
Alarm word.
Status word.
Control word.
Extended status word.
Events are logged with value and time stamp in ms. The
time interval between 2 events depends on how often
events occur (maximum once every scan time). Data
logging is continuous, but if an alarm occurs, the log is
saved and the values can be viewed on the display. This
feature is useful, for example when carrying out service
following a trip. View the historic log contained in this
parameter via the serial communication port or via the
display.
15-20 Historic Log: Event
Array [50]
Range:
0
[0 - 255 ]
*
15-21 Historic Log: Value
Array [50]
Range:
0
[0 -
*
2147483647 ]
206
VLT
Function:
View the event type of the logged events.
Function:
View the value of the logged event.
Interpret the event values according to
Table 3.30:
Digital input
Decimal value. See
parameter 16-60 Digital
Input for description after
converting to binary
value.
Digital output
Decimal value. See
(not
parameter 16-66 Digital
monitored in
Output [bin] for a
this SW
description after
release)
converting to binary
value.
Warning word Decimal value. See
parameter 16-92 Warning
Word for a description.
Alarm word
Decimal value. See
parameter 16-90 Alarm
Word for a description.
Danfoss A/S © 10/2018 All rights reserved.
®
AutomationDrive FC 301/302
15-21 Historic Log: Value
Array [50]
Range:
15-22 Historic Log: Time
Array [50]
Range:
0 ms
[0 - 2147483647
*
ms]

3.15.8 15-3* Alarm Log

Parameters in this group are array parameters where up to
10 fault logs can be viewed. 0 is the most recent logged
data, and 9 is the oldest. Fault codes, values, and time
stamp can be viewed for all logged data.
15-30 Fault Log: Error Code
Range:
0
[0 - 65535 ] View the fault code and look up its meaning in
*
15-31 Fault Log: Value
Array [10]
Range:
0
[-32767 - 32767 ] View an extra description of the error.
*
15-32 Fault Log: Time
Array [10]
Range:
0 s
[0 - 2147483647 s] View the time when the logged event
*
Function:
Status word
Decimal value. See
parameter 16-03 Status
Word for a description
after converting to binary
value.
Control word
Decimal value. See
parameter 16-00 Control
Word for a description.
Extended
Decimal value. See
status word
parameter 16-94 Ext. Status
Word for a description.
Table 3.30 Logged Events
Function:
View the time at which the logged
event occurred. Time is measured in
ms since frequency converter start. The
maximum value corresponds to
approximately 24 days, which means
that the count restarts at 0 after this
time period.
Function:
chapter 6 Troubleshooting.
Function:
This parameter is mostly used with alarm
38, internal fault.
Function:
occurred. Time is measured in s from
frequency converter start-up.
MG33MP02