3.7.6 6-5* Analog Output 1

Parameters for configuring the scaling and limits for analog
output 1, that is terminal 42. Analog outputs are current
outputs: 0/4–20 mA. Common terminal (terminal 39) is the
same terminal and has the same electrical potential for
analog common and digital common connection.
Resolution on analog output is 12 bit.
6-50 Terminal 42 Output
Option:
[0]
No
operation
[52]
MCO
0-20mA
[53]
MCO
4-20mA
[58]
Actual
Position
[59]
Actual
Position
4-20mA
[100] Output
frequency
[101] Reference
138
®
VLT
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the filter time constant. This
constant is a first-order digital low-pass
filter time for suppressing electrical noise
in terminal X30/12. A high value improves
dampening but also increases the delay
through the filter.
Function:
Select the function of terminal 42 as an
analog current output. Depending on the
selection, the output is either a 0–20 mA or
4–20 mA output. The current value can be
read out in the LCP in
parameter 16-65 Analog Output 42 [mA].
Indicates no signal on the analog output.
NOTICE
This option is available only with
software version 48.XX.
The actual position. 0–20 mA corresponds to
parameter 3-06 Minimum Position to
parameter 3-07 Maximum Position.
NOTICE
This option is available only with
software version 48.XX.
The actual position. 4–20 mA corresponds to
parameter 3-06 Minimum Position to
parameter 3-07 Maximum Position.
0 Hz = 0 mA; 100 Hz = 20 mA.
Parameter 3-00 Reference Range [Min - Max]
0% = 0 mA; 100% = 20 mA
Danfoss A/S © 10/2018 All rights reserved.
AutomationDrive FC 301/302
6-50 Terminal 42 Output
Option:
[102] Feedback
[103] Motor
Current
[104] Torque rel to
limit
[105] Torq relate
to rated
[106] Power
[107] Speed
[108] Torque
[109] Max Out
Freq
[113] PID Clamped
Output
[119] Torque %
lim
[130] Output freq.
4-20mA
[131] Reference
4-20mA
[132] Feedback
4-20mA
[133] Motor cur.
4-20mA
Function:
Parameter 3-00 Reference Range [-Max - Max]
-100% = 0 mA; 0% = 10 mA; +100% = 20
mA.
The value is taken from parameter 16-37 Inv.
Max. Current. The inverter maximum current
(160% current) is equal to 20 mA.
Example: Inverter normal current (11 kW) is
24 A. 160 %=38.4 A. Motor normal current is
22 A, the readout is 11.46 mA.
20 mA x 22 A
= 11 . 46 mA
38 . 4 A
In case the normal motor current is equal to
20 mA, the output setting of
parameter 6-52 Terminal 42 Output Max Scale
is:
I
 x 100
38 . 4 x 100
VLT
Max
=
= 175 %
I
22
Motor
Norm
The torque setting is related to the setting
in parameter 4-16 Torque Limit Motor Mode.
The torque is related to the motor torque
setting.
Taken from parameter 1-20 Motor Power
[kW].
Taken from parameter 3-03 Maximum
Reference. 20 mA equals the value in
parameter 3-03 Maximum Reference.
Torque reference related to 160% torque.
0 Hz = 0 mA, parameter 4-19 Max Output
Frequency = 20 mA.
0 Hz = 4 mA, 100 Hz = 20 mA.
Parameter 3-00 Reference Range [Min-Max]
0% = 4 mA; 100% = 20 mA
Parameter 3-00 Reference Range [-Max-Max]
-100% = 4 mA; 0% = 12 mA; +100% =
20 mA.
The value is taken from parameter 16-37 Inv.
Max. Current. The inverter maximum current
(160% current) is equal to 20 mA.
Example: Inverter normal current (11 kW) is
24 A. 160% = 38.4 A. Motor normal current
is 22 A, the readout is 11.46 mA.
16 mA x 22 A
+ 4 mA = 13 . 17 mA
38 . 4 A
In case the normal motor current is equal to
20 mA, the output setting of
parameter 6-52 Terminal 42 Output Max Scale
is:
MG33MP02

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 301

Table of Contents