Manual Initialization - Danfoss VLT AutomationDrive FC 302 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

How to Program

Manual initialization

1.
Disconnect from mains and wait until the display
turns off.
2.
2a
Press [Status] - [Main Menu] - [OK] at
the same time while powering up the
LCP 102, graphical display.
2b
Press [Menu] - [OK] while powering up
the LCP 101, numerical display.
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed
according to default settings.
This procedure initializes all except:
Parameter 15-00 Operating hours.
Parameter 15-03 Power Up's.
Parameter 15-04 Over Temp's.
Parameter 15-05 Over Volt's.
NOTICE
A manual initialization also resets serial communication,
RFI filter settings (parameter 14-50 RFI Filter), and fault
log settings.
MG33MP02
Programming Guide
Danfoss A/S © 10/2018 All rights reserved.