Warning Current Low; Warning Current High; Warning Speed Low/High; Warning Reference Low/High - Danfoss VLT AutomationDrive FC 302 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Parameter Descriptions

4-50 Warning Current Low

Range:
Function:
0 A
[ 0 - par.
Enter the I
*
LOW
4-51 A]
falls below this limit, the display reads Current
Low. The signal outputs can be programmed to
produce a status signal on terminal 27 or 29 (FC
302 only) and on relay output 01 or 02 (FC 302
only). Refer to Illustration 3.33.

4-51 Warning Current High

Range:
Function:
Size
[ par.
Enter the I
related
4-50 - par.
current exceeds this limit, the display
*
16-37 A]
reads Current High. The signal outputs can
be programmed to produce a status
signal on terminal 27 or 29 (FC 302 only)
and on relay output 01 or 02 (FC 302
only). Refer to Illustration 3.33.
4-52 Warning Speed Low
Range:
Function:
0 RPM
[ 0 - par.
Enter the n
*
4-53 RPM]
exceeds this limit, the display reads Speed
low. The signal outputs can be programmed
to produce a status signal on terminal 27 or
29 (FC 302 only) and on relay output 01 or
02 (FC 302 only).
4-53 Warning Speed High
Range:
Function:
Size
[ par.
Enter the n
related
4-52 -
speed exceeds this value, the display
*
60000
reads Speed high. The signal outputs can
RPM]
be programmed to produce a status
signal on terminals 27 or 29 and on relay
outputs 01 or 02. Refer to
Illustration 3.33.
4-54 Warning Reference Low
Range:
-999999.999
[ -999999.999 -
*
par. 4-55 ]
4-55 Warning Reference High
Range:
Function:
999999.999
[ par. 4-54 -
Enter the upper reference limit.
*
999999.999 ]
When the actual reference exceeds
this limit, the display reads Ref
MG33MP02
Programming Guide
value. When the motor current
value. When the motor
HIGH
value. When the motor speed
LOW
value. When the motor
HIGH
Function:
Enter the lower reference limit.
When the actual reference drops
below this limit, the display
indicates Ref
. The signal
LOW
outputs can be programmed to
produce a status signal on
terminal 27 or 29 (FC 302 only)
and on relay output 01 or 02 (FC
302 only).
.
high
Danfoss A/S © 10/2018 All rights reserved.
4-55 Warning Reference High
Range:
Function:
The signal outputs can be
programmed to produce a status
signal on terminal 27 or 29 (FC 302
only) and on relay output 01 or 02
(FC 302 only).
4-56 Warning Feedback Low
Range:
Size
[ -999999.999 -
related
par. 4-57
*
ReferenceFeed-
backUnit]
4-57 Warning Feedback High
Range:
Size
[ par. 4-56 -
related
999999.999
*
ReferenceFeed-
backUnit]
4-58 Missing Motor Phase Function
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
The missing motor phase function detects
whether the motor phase is missing during
motor rotation. Shows alarm 30, 31, or 32 in the
event of a missing motor phase. Enable this
function to avoid motor damage.
See also chapter 3.5.5 Combinations of parameters
4-58 and 4-59.
[0] Disabled
The frequency converter does not issue a missing
motor phase alarm. Not recommended due to
risk of motor damage.
[1] Trip 100
For a quick detection time and alarm in the
ms
event of a missing motor phase.
[2] Trip 1000
ms
[3] Trip
Special option relevant for crane applications
100ms
when lowering a small load that lets the
3ph
frequency converter avoid false detections of
detec.
missing motor phase.
Function:
Enter the lower feedback limit.
When the feedback drops below
this limit, the display reads
Feedb
. The signal outputs can
Low
be programmed to produce a
status signal on terminal 27 or
29 (FC 302 only) and on relay
output 01 or 02 (FC 302 only).
Function:
Enter the upper feedback limit.
When the feedback exceeds this
limit, the display reads Feedb
.
High
The signal outputs can be
programmed to produce a status
signal on terminal 27 or 29 (FC
302 only) and on relay output 01
or 02 (FC 302 only).
93
3
3