VLT® PTC Thermistor Card MCB 112
Operating Guide
6.
At commissioning and after modification of the plant, check the sensor resistance with a suitable measuring instrument. If
the resistance between terminals 1 and 2 is <50 Ω, examine the sensor circuit for a short circuit.
3.5 Maximum Current on MCB 112
Motor protection
MCB 112 PTC
Thermistor Option B
ZIEHL industrie-elektronik GmbH + Co KG
Code No. 130B1137
Daimlerstrasse 13, 74523 Schwäbisch Hall
0102
!
SEE MANUAL FOR
ADDITIONAL INSTRUCTIONS
PTC
T1
T2
NC
NC
NC
NC
X44
1
2
3
4
5
12 13 18 19 27 29 32 33 20 37
TP
TP
PTC
M 3~
Illustration 5: Wiring Diagram
T10
10 mA
T12
60 mA
Terminal 12
24 V DC supply voltage
Terminal 13
24 V DC supply voltage
T37 (X44/12)
Output terminal on the VLT
Terminal 37
Input terminal on the control card.
X44/10
Logic output signals the status in case of failure.
3.6 Wiring of STO
Procedure
1.
Remove the jumper wire between control terminals 37 and 12, or 13.
Cutting or breaking the jumper is not sufficient to avoid short circuiting.
16 | Danfoss A/S © 2022.08
www.ziehl.de
PTB 14 ATEX 3012U
II (2) G [Ex eb Gb] [Ex db Gb]
II (2) D [Ex tb Db]
10
20-28 VDC
10 mA
12
20-28 VDC
60 mA
LOGIC
SAFE STOP
NC
NC
NC
OUT
NC
T37
6
7
8
9
10
11
12
PTC Thermistor Card MCB 112 option.
®
Installation
AQ267038105120en-000101 / 130R0104
Need help?
Do you have a question about the VLT PTC Thermistor Card MCB 112 and is the answer not in the manual?
Questions and answers
Is PTC Thermistor card required in PESO certification also?