Configurable Control Word Ctw - Danfoss VLT AutomationDrive FC 302 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Parameter Descriptions
8-13 Configurable Status Word STW
Option:
[21]
Thermal warning
[30]
Brake fault (IGBT)
[40]
Out of ref range
[49]
Derate active
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic Rule 0
[71]
Logic Rule 1
[72]
Logic Rule 2
[73]
Logic Rule 3
[74]
Logic Rule 4
[75]
Logic Rule 5
[80]
SL digital out A
[81]
SL digital out B
[82]
SL digital out C
[83]
SL digital out D
[84]
SL digital out E
[85]
SL digital out F
[86]
ATEX ETR cur. alarm
[87]
ATEX ETR freq. alarm
[88]
ATEX ETR cur. warning
[89]
ATEX ETR freq. warning
[90]
Safe Function active
[91]
Safe Opt. Reset req.
[92]
IGBT-cooling
[181] Prev. Maintenance
[200] User Defined Alerts
[231] In Power Lim. Mot.
[232] In Power Lim. Gen.
[233] In Power Limit

8-14 Configurable Control Word CTW

This is an array parameter with 16 elements, 1 element for each
bit in range 0–15. Each of the bits can be configured to any of
the following options.
Option:
Function:
This parameter is not valid in software
versions before 4.93.
NOTICE
Options in this block are only
available for 48.XX.
[0]
None
The frequency converter ignores the
information in this bit.
[1]
Profile default
The functionality of the bit depends on
*
the selection in parameter 8-10 Control
Word Profile.
MG33MP02
Programming Guide
Function:
Danfoss A/S © 10/2018 All rights reserved.
8-14 Configurable Control Word CTW
This is an array parameter with 16 elements, 1 element for each
bit in range 0–15. Each of the bits can be configured to any of
the following options.
Option:
Function:
[2]
CTW Valid,
If set to 1, the frequency converter
active low
ignores the remaining bits of the control
word.
[3]
Safe Option
This function is only available in bits 12–
Reset
15 of the control word if a safety option
is mounted in the frequency converter.
The reset is executed on a 0⇒1
transition and resets the safety option as
set in parameter 42-24 Restart Behaviour.
[4]
PID error inverse Inverts the resulting error from the
process PID controller. Available only if
parameter 1-00 Configuration Mode is set
to [6] Surface Winder, [7] Extended PID
Speed OL, or [8] Extended PID Speed CL.
[5]
PID reset I part
Resets the I-part of the process PID
controller. Equivalent to
parameter 7-40 Process PID I-part Reset.
Available only if parameter 1-00 Configu-
ration Mode is set to [6] Surface Winder,
[7] Extended PID Speed OL, or [8]
Extended PID Speed CL.
[6]
PID enable
Enables the extended process PID
controller. Equivalent to
parameter 7-50 Process PID Extended PID.
Available only if parameter 1-00 Configu-
ration Mode is set to [6] Surface Winder,
[7] Extended PID Speed OL, or [8]
Extended PID Speed CL.
[7]
External
Interlock
[10]
Bit 10 = 0 >
CTW Timeout
[11]
Start Homing
[12]
Activate Touch
[13]
Sync. to Pos
Select positioning in synchronization
Mode
mode.
[14]
Ramp 2
Select between ramp 1 (parameter group
3-4* Ramp 1) and ramp 2 (parameter
group 3-5* Ramp 2).
[15]
Relay 1
Control relay 1.
[16]
Relay 2
Control relay 2.
[17]
Speed Mode
Select the speed mode when [9]
Positioning or [10] Synchronization is
selected in parameter 1-00 Configuration
Mode. Speed reference is set by
reference resource 1 or fieldbus REF1
relative to parameter 3-03 Maximum
Reference.
3
3
157

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 301

Table of Contents