Removing Safety Shield; Atevo With Selectable Input Voltage - Optional; Determining If Multi-Tap Option Is Present - HindlePower ATevo Series Operating/Service Instructions Manual

Microprocessor-controlled float battery charger
Hide thumbs Also See for ATevo Series:
Table of Contents

Advertisement

2 Wiring
2.2 Removing Protective Safety Shield
! WARNING
must always be installed when charger is in operation and/or
energized.
STEPS
• A standard flat blade screwdriver is required.
• Open the ATevo front panel door to access safety shield.
• Remove the two (2) screws that attach the safety shield to the
ATevo, one above AC Input Breaker (CB1), the other below the
DC Output Breaker (CB2).
• Grab the safety shield on both left and right sides, and gently lift
up and off of AC Input and DC Output Circuit Breakers.
• Reverse procedure for reinstalling the safety shield.

2.3 ATevo with Selectable Input Voltage - optional

ATevo may be equipped with a multi-tap ac input voltage, in two (2)
options for field configuration:
• 120, 208 or 240 Vac 60Hz - 'MT1' in smart part number
• 115, 220, or 240 Vac 50/60Hz - 'MT2' in smart part number

2.3.1 Determining if Multi-Tap Option is Present

Check the ATevo nameplate. If the ac input voltage is listed as
120/208/240 or 115/220/240 Vac, the ATevo is equipped with the
multi-tap option. If the nameplate is not visible:
• Open the ATevo front panel door.
• Behind the safety shield, look for a gray terminal block directly
above the AC Input Circuit Breaker (CB1).
» Reference the input voltage selection silk-screened on the
center-right of the safety shield.
» If this terminal block is present, the ATevo is equipped with
the multi-tap ac input voltage option.
14
To prevent injuries, the ATevo safety shield
ATevo

Hide quick links:

Advertisement