14.3.
14.3. Replacing Defective Components
Replacing Defective Components
High voltages appear at several points inside ATevo. Use extreme caution
when working inside enclosure. Do not attempt to work inside ATevo unless
you are a qualified technician or electrician.
Disconnect and lock out all power from ATevo before starting to remove or
replace any components. Turn OFF ac power at distribution panel upstream
from ATevo. Disconnect battery from DC Output Circuit Breaker (CB2+/-). Wait
several minutes to allow voltages in dc filter electrolytic capacitors (C1x/C2)
to bleed off.
Printed circuit boards are sensitive to damage from static discharges. Leave
replacement pc boards in anti-static bags until you are ready to install them.
Ground yourself before handling board, by touching ground stud on back of
door. Always handle printed circuit boards by their edges.
Each topic in this section provides instructions for replacing a different component if defective.
•
Removing Safety Shield
•
Replacing Main Control Board
•
Replacing Serial Communications Adapter
•
Replacing Ethernet Adapter
•
Replacing Rectifier / Heat Sink Assembly
•
Replacing Power Board
•
Replacing Auxiliary I/O Board
•
Replacing Filter Capacitor Board Assembly
•
Replacing Eliminator Filter Capacitor (C2) – optional
•
Replacing Circuit Breakers
•
Replacing Power Isolation Transformer
•
Replacing Filter Inductors
•
Replacing DC Power Supply
•
Replacing MOV Surge Suppressor Board
Copyright HindlePower Inc. 2021
ATevo O&SI - 3PH Input (16-1000 Adc) - 1.1_en
Last modified: 3 August 2023