2 Wiring

2.5 Making DC Output Connections

Installer is responsible to provide suitable dc output, battery, and dc
load wiring.
Follow these steps to connect the battery to ATevo:
1. Size the dc wiring to minimize voltage drop. Acceptable wire
size depends on the installation. As a guideline, voltage
drop should not exceed 1% of nominal output voltage at
full current. Refer to the following table to determine the
voltage drops for various wire sizes, currents and distances.
Voltage Drop per 100ft / 30.5m of Wire
Wire
Size
(AWG)
#16
2.5V
#14
1.6V
#12
1.0V
#10
0.63V
#8
0.40V
#6
0.25V
#4
0.16V
EXAMPLE:
2. ATevo is factory wired to regulate output voltage at the
output terminals. If total voltage drop is greater than 1%
(e.g. 1.3V for a 130 Vdc system), remote sense wiring is
recommended (see Section 11).
3. Do not run external ac and dc power wiring through the
same conduit.
4. Facility-specific installation requirements take precedence.
18
Wire Sizing Chart
(for copper at 68 °F / 20 °C)
DC Current (Amperes)
6
12
5.0V
3.2V
2.0V
1.3V
0.80V
0.50V
0.32V
100ft / 30.5m of #8 AWG wire at 16A has a 1.1V drop.
ATevo
16
20
6.7V
8.2V
4.2V
5.3V
2.6V
3.3V
1.7V
2.1V
1.1V
1.3V
0.66V
0.83V
0.42V
0.52V
25
10.5V
6.6V
4.2V
2.6V
1.7V
1.1V
0.65V

Hide quick links: