13.5.3 Forced Load Sharing Alarms

The following alarms related to Forced Load Sharing are logged and
can be configured to trigger the common alarm:
• 'Loadshare Not Ready' – displays on ATevo that is not ready to
share load for reasons including no ac power, low ac power,
HVDC shutdown, HLD shutdown, or open DC Breaker (CB2)
• 'Loadshare Comm Failure' – displays when an ATevo configured
for Forced Load Sharing is not receiving any load share
messages
• 'Loadshare Indep Mode' – indicates virtual independence
between Forced Load Sharing ATevos, only reported on the
Primary ATevo
13.6 Temperature Comp. with Forced Load Sharing
The recommended practice for an ATevo Forced Load Sharing
application, which uses temperature compensation, is for each ATevo
to have a battery temperature probe (A10) and have temperature
compensation initiated.

13.7 Battery Open Alarm for Forced Load Sharing

The recommended practice for Forced Load Sharing which employs
periodic Open Battery Testing is to only enable the test on the
Primary ATevo. During load sharing, the Primary ATevo will dictate
the battery open test voltage setting to all Secondary chargers when
a scheduled test runs. It is always possible to manually start a
Battery Open Test from a Primary or Secondary when load sharing is
active.

13.8 Timed Equalize with Forced Load Sharing

If a timed equalize is in progress, all ATevos sharing load will depict
the Equalize Time Remaining, alternating with the Volt/Ammeter
display. If the ATevos go independent while timed equalize is active,
they will continue timed equalize. If a Primary ATevo goes offline,
the Secondary ATevo will continue in equalize mode until the Primary
ATevo come back on-line. The Primary ATevo and all Secondary
ATevos will switch back to float mode after the Primary ATevo resets.