Wiring Relays On Auxiliary I/O Board; Wiring Temperature Compensation Probe - HindlePower ATevo Series Operating/Service Instructions Manual

Microprocessor-controlled float battery charger
Hide thumbs Also See for ATevo Series:
Table of Contents

Advertisement

PROCEDURE
1. Allow 30in / 762mm of wire inside enclosure, and trim
excess.
2. Route annunciator wires to ATevo front panel door by
following existing harness past door hinge.
3. Use two (2) wire ties and allow a 4-6in / 102-153mm
loop for the hinge.
4. Trim wires to length to connect to alarm terminal block
(A1-TB6), and strip 0.25in / 6.4mm of insulation.
5. Make connections at A1-TB6 and tighten compression
screws.
NOTES
1. Alarm contacts are rated at 0.5A / 125 Vac or Vdc.
2. Common Alarm relay terminal block (A1-TB6) is
compression type, accepting wire sizes #22-14 AWG.
3. Terminals are labeled in non-alarm condition.
4. If user alarm contacts (A1-TB6) are to drive inductive dc
loads (e.g. a larger dc relay) an external protective diode
must be installed at the dc relay to avoid equipment
damage. Refer to Application Note (JD5011-00).

2.8 Wiring Relays on Auxiliary I/O Board

When provided, the optional Auxiliary Alarm I/O Board (A4) is
mounted to the heat sink, above the Power Board (A2) on the
left side of the ATevo. See Section 12 for more information and
wiring instructions.

2.9 Wiring Temperature Compensation Probe

The battery temperature compensation, or 'TempCo', probe
(A10) contains a temperature-dependent resistor in an epoxy
module. When used, this probe is installed on the battery. See
Section 11 for more information and wiring instructions.
ATevo
2 Wiring
21