12 Auxiliary Inputs/Outputs
To change the low scale value:
MENU > AUX INPUTS > 'Analog Input Configuration' > select input
(as shown in Section 12.6.1) > '0V=:' > set desired digits
• This number must represent the primary value when the input
value is 0 V. If no scaling is required, set 0.
To change the high scale value assigned to the Analog Input:
'10V=:' > set desired digits
• This number must represent the primary value when the input
value is 10.0 Vdc. If no scaling is required, set 10.

12.6.5 Analog Input Alarm and Trigger Assignment

The ATevo can generate various alarms based on Analog Input
values. There are several triggers that can be assigned to define
the alarm condition. An alarm can be generated if the analog value
is above a threshold, below a threshold, within a defined range, or
outside a defined range. The threshold parameter(s) required will
depend on the trigger type selected. Threshold parameters must
be entered based on the scaling values such that the thresholds
assigned are within the range of the scaling.
116