Remote Sense; Atevo Remote Voltage Sense; Remote Sense Connection - HindlePower ATevo Series Operating/Service Instructions Manual

Microprocessor-controlled float battery charger
Hide thumbs Also See for ATevo Series:
Table of Contents

Advertisement

11 Remote Sense

11.1 ATevo Remote Voltage Sense

ATevo regulates dc output voltage as measured at the charger's
output connection (CB2+/-). The Remote Voltage Sense feature
permits ATevo to monitor and regulate the dc output voltage at the
battery. This feature is useful when long battery cables, causing
resistive voltage-drop, connect ATevo to the battery. All ATevo
chargers can be wired to utilize this feature.

11.2 Remote Sense Connection

Remote sensing:
• Compensates for voltage drop in dc wiring between ATevo and
the battery.
• Directly monitors battery or dc bus voltage. The front panel
meter displays actual voltage at the battery or dc bus.
SCHEMATIC
REMOTE SENSE
ATevo
RECTIFIER
To wire ATevo for remote sensing, install twisted-pair cabling from
the remote sense terminals to the battery terminals or dc bus. ATevo
control circuitry measures dc voltage at the battery terminals and
controls charger output to maintain battery voltage at the desired
float or equalize voltage.
! CAUTION
sense wiring. Install a 1.0A fuse at the battery or dc bus end of each
remote sense cable.
94
POS
LEADS
DC BUS
ATevo cannot protect against short circuits in remote
ATevo
NEG
BREAKER
BATTERY

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents