12 Auxiliary Inputs/Outputs
To assign an alarm trigger to an Analog Input:
MENU > AUX INPUTS > 'Analog Input Configuration' > select input
(as shown in Section 12.6.1) > 'Trigger:'
12.6.6 Analog Input Alarm Threshold Assignment
ATevo can generate alarms based on Analog Input value. Alarm
thresholds are the set points at which an alarm occurs. Each Analog
Input can be assigned an alarm with a trigger. Some triggers only
require one threshold. The 'above a threshold' alarm trigger requires
a 'high threshold' set point, the 'below a threshold' trigger requires
a 'low threshold set point'. Other range based triggers require both
a 'low threshold' and a 'high threshold' set point to determine the
range. ATevo will automatically determine which thresholds are
required based on the trigger selected. Always set the trigger before
adjusting the thresholds.
To adjust the low level threshold set point for a trigger for an Analog
Input alarm:
MENU > AUX INPUTS > 'Analog Input Configuration' > select input
(as shown in Section 12.6.1) > 'Trigger:' > 'Low threshold:' > set digits
117