Mounting Atevo; Wall-Mounting - HindlePower ATevo Series Operating/Service Instructions Manual

Microprocessor-controlled float battery charger
Hide thumbs Also See for ATevo Series:
Table of Contents

Advertisement

1 Receiving & Mounting

1.7 Mounting ATevo

Mount the ATevo Style-5054 enclosure to easily access the front
panel AC Input (CB1) and DC Output (CB2) Circuit Breakers. Choose
from the following mounting methods:

1.7.1 Wall-Mounting

Wall-mounting is the standard method. When wall-mounting ATevo,
consider the following:
1. Refer to the Style-5054 enclosure outline drawing in Appendix B.
2. The wall must be strong enough to properly support ATevo's
weight, plus a safety factor. Refer to Weight Table in Section
1.6.1. The weight of ATevo may be different, depending on the
features, options, and accessories ordered with the unit.
3. Select conduit entrances with planned ac input and dc output
wiring in mind. By using pre-fab knockouts on enclosure sides
or bottom, the cabinet shroud can be removed for internal
servicing without removing ATevo from the wall.
4. Location requirements:
» Free of drips and splatter. If falling particles and liquids are
a problem, install a NEMA Type 2 drip shield accessory.
» Between 0 and 122 °F / -18 and 50 °C, with relative humidity
between 0% and 95% non-condensing.
» Must be free of flammable or explosive materials.
5. Maintain at least 6in / 152mm of free air on all vented surfaces
for cooling.
6. Allow at least 36in / 914mm front clearance for operation and
maintenance.
PROCEDURE
Install four (4) 0.25in / 6.4mm anchor bolts (not supplied) rated
to support ATevo's weight plus a minimum safety factor of two (2)
times, into the wall. Place ATevo onto anchor bolts, add appropriate
mounting hardware, and tighten securely. Refer to the following
graphics for ATevo wall-mounting pattern and specification.
4
ATevo

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents