4 Startup & Configuration
By default, the Main Board Relay is configured to indicate the status
of the Common Alarm, but this may be changed to indicate the
status of any ATevo alarm or status state.
If this relay is configured to be 'latching', it will change to the active
state after the configured time delay, and remain in the active state
even if the alarming condition is no longer present. Latched relays
must be cleared manually to ensure that they are acknowledged. See
Section 7.6 for instructions on how to clear (or reset) latched relays.
To change the Common Alarm Relay configuration:
MENU > RELAYS > 'Main board relay'.
To change the relay's assigned fault condition:
'Fault:' > select desired condition