PROCEDURE
1. Use a dc disconnect switch or circuit breaker between ATevo and
the dc bus. This device should have lockout capability to allow
ATevo to be disconnected from the dc bus for maintenance.
2. Remove safety shield (see Section 2.2).
3. Run dc wiring to Output Circuit Breaker (CB2).
4. Connect wires to appropriate locations on the DC Output
Breaker (CB2+/-) as indicated on drawing above.
5. Using a flat-blade screwdriver, securely tighten compression
screws on DC Output Breaker Terminals (CB2+/-).
6. Reinstall safety shield after you have made and checked all
connections.
ATevo
2 Wiring
19