7 Alarms & Indicators
After executing this command the number between '( )' will change
to '0' indicating all latched relays are cleared.

7.7 Battery Open Test

The Battery Open Test feature will detect if the connection between
the battery and ATevo has been lost, or if there is a weak or faulty
battery. The test lowers the charger voltage and verifies whether
the battery can assume the present dc load. This test can be run
manually or according to a set schedule.
The Battery Open Test will fail if the dc bus drops below a
configurable voltage set point. When such occurs the test aborts
immediately and ATevo will raise output voltage back to the present
Float or Equalize setting. Test duration is configurable as seen below.
If the test fails, a Battery Open alarm is generated and can only be
cleared by the Unlatch Battery Open Alarm control.

7.7.1 Battery Open Test Settings

To access and configure Battery Open Test settings:
MENU > TESTING > 'Test Settings'
To configure test duration:
'Run test for up to:' > adjust duration