PROCEDURE
1. De-energize and lock out all ac and dc voltages to ATevo.
2. Allow internal voltages to dissipate.
3. Remove safety shield and verify no hazardous voltages are
present with a voltmeter.
4. Mount probe (A10) on a clean, dry surface on or as close to
battery as possible.
Do NOT mount probe on:
» unpainted wood
» bare galvanized metal
» plastic surfaces
NOTICE
Consult battery manufacturer for mounting restrictions
and adhesive compatibilities.
5. To apply probe, clean mounting surface with isopropyl alcohol
and dry thoroughly.
6. Remove protective backing from double-faced adhesive tape on
probe, and press onto surface.
7. Install supplied cable:
» Route end of cable that has two (2) stripped wires and a
quick-connect terminal to the inside of ATevo cabinet.
» Leave 30in / 762mm of cable inside enclosure. Run cable
through a conduit that does not contain power wiring.
» Route other end of cable to probe at the battery, and coil up
excess cable.
» Make sure all wiring conforms to NEC, local, and site
requirements
10 Battery Temperature Compensation