12 Auxiliary Inputs/Outputs
12.5.4 Binary Input Alarm Enable
The binary active alarm enable assignment determines whether the
Binary Input will generate an alarm, when it senses the alarmed
state. Alarms generated by Binary Inputs will appear by their
configured name in the alarm list and on the bottom of the HOME
screen.
To enable or disable the Binary input alarm function:
MENU > AUX INPUTS > 'Binary Input Configuration' > select input
from options (as shown in Section 12.5.1) > 'Alarm:' > select from 2
alarmed states
12.5.5 Binary Input Action Assignment
The Binary Input action assignment links the Binary Input to a
changer control. Examples of a charger control include rectifier
remote shutdown, or float/equalize mode control. ATevo will execute
assigned charger control when the Binary Input is in the active state.
To assign a control to a Binary Input:
MENU > AUX INPUTS > 'Binary Input Configuration' > select input
from options (as shown in Section 12.5.1) > 'Action:' > select from 2
actions