11.3 Procedure for Wiring Remote Sense
Route twisted-pair cable between the battery and ATevo charger, and
make the connections described below BEFORE you move the Remote
Sense enable jumpers to enable the Remote Sense feature.
Preparation:
• De-energize and lock out all ac and dc voltages to ATevo.
• Allow internal voltages to dissipate.
• Remove safety shield.
• Verify no hazardous voltages are present with a voltmeter.
• Route a #16 AWG twisted-pair cable from the bottom of the
ATevo Power Board (A2) to the desired battery sense location.
• Designate one (1) wire of twisted pair as 'DC(+)' and other as
'DC(-)'.
• Locate Remote Sense terminal block (A2-TB1) on the bottom
front of the ATevo Power Board.
ATevo
11 Remote Sense
95