» Route TempCo cable to lower end of Power Board (A2).
» Locate TB8 and insert one (1) of each of the stripped wires
from the twisted pair into each location on the terminal
block (A2-TB8). Connection Points are not polarity sensitive.
» Locate the EARTH quick-connect terminal at the bottom
of Power Board (A2). Carefully pull off the quick-connect
terminal and wire from the EARTH terminal.
» Plug the quick-connect terminal attached to the end of the
TempCo cable's shield wire onto the Power Board's EARTH
terminal.
» Connect the quick-connect terminal removed from the EARTH
terminal to the 'piggy-back' terminal on the end of the
TempCo cable's shield wire.
» Fasten the TempCo cable to existing wire harness with
plastic wire ties.
9. At the battery, connect the quick-connect terminals to the
TempCo probe (A10). Connection points are not polarity
sensitive. Coil up and wire-tie any excess wire to prevent
damage.
10. Confirm that:
» All connections are secure.
» Both the TempCo shield and the original ground wire are
connected to the EARTH quick-connect terminal (A2-EARTH).
» The twisted-pair wires of the TempCo cable are connected to
the 2-position terminal block on the Power Board (A2-TB8).
11. Replace the safety shield and close the front panel door.
12. Restart the ATevo.

10.2.1 Configuring the TempCo Option

ATevo will need to be configured to enable the TempCo probe (A10)
and to select the battery type. See Sections 4.3.9 and 4.3.10 for
instructions.
10 Battery Temperature Compensation
ATevo
91