1 Receiving & Mounting

1.7.2 Floor-Mounting

To install ATevo onto a horizontal surface, the standard enclosure
does not need to be modified, but a special floor mounting accessory
is required. The kit includes a set of mounting brackets that elevate
the top of ATevo approximately 47in /1194mm above floor level,
with provisions for floor anchoring. The kit also includes appropriate
hardware and installation instructions for the floor-mounting
procedure.
When floor-mounting ATevo, consider the following:
1. Locate anchor bolt holes at least 4.25in /108mm from any wall,
to allow clearance behind the mounting brackets.
2. Select conduit entrances with planned ac input and dc output
wiring in mind. By using pre-fab knockouts on enclosure sides
or bottom, the cabinet shroud can be removed for internal
servicing without removing ATevo from the floor stand.
3. Location requirements:
» Free of drips and splatter. If falling particles and liquids are
a problem, install a NEMA Type 2 drip shield accessory.
» Between 0 and 122 °F / -18 and 50 °C, with relative humidity
between 0% and 95% non-condensing.
» Must be free of flammable or explosive materials.
4. Maintain at least 6in /152mm of free air on all vented surfaces
for cooling.
5. Allow 36in /914mm front clearance for operation and
maintenance.
PROCEDURE
Install four (4) 0.25in / 6.4mm anchor bolts (not supplied) rated
to support the unit weight plus a minimum safety factor of two (2)
times, into floor.
Assemble the floor-mounting accessory on to the anchor bolts as
shown. Place ATevo onto vertical posts, add appropriate mounting
hardware, and tighten.
Refer to the following graphics for floor mounting patterns and
enclosure footprints.