13.4.1 Configuring ATevo for Forced Load Sharing

You must assign a charger ID to each ATevo connected in forced load
sharing. Configure one as the Primary and all other chargers as
Secondary chargers.
To configure an ATevo for Forced Load Sharing:
MENU > COMMUNICATION > Port 'X' setup
• 'X' is either '2' or '3' for Port 2 or Port 3. The Port configured
for forced load share must be the port that the Serial
Communications Adapter is plugged into that is wired to the
Forced Load Sharing network.
• Select 'loadshare P' for the Primary ATevo, or 'loadshare S' for
Secondary ATevos.
Press the EDIT/ENTER button to accept the new selection. The
charger ID may now be changed. Press the ESC button to return
to the previous screen. If a port setting was changed, the ATevo
will prompt to RESET. Select YES to RESET the ATevo. The new port
settings will not become active until after the ATevo is RESET.
13 Forced Load Sharing