2.3.2 Verifying Multi-Tap AC Input Voltage Setting

2.3.3 Modifying Multi-Tap AC Input Voltage Setting

! WARNING
jumper, shut down ATevo and lock out ac and dc power supplies.
Turning off (opening) the ATevo internal circuit breakers does not
eliminate live voltages inside the enclosure.
• Standard flat blade screwdriver is required.
• Remove the ATevo safety shield per Section 2.2.
• Locate the multi-tap terminal block.
• Set locations of RED jumpers for desired ac input voltage, per
Section 2.3.2.
» Carefully pry out jumpers in existing locations.
» Re-install jumpers into new (correct) locations.
• Re-check jumper locations and confirm jumpers are properly
seated.
Before you connect ac power to ATevo, inspect
the present ac input voltage setting, and
confirm the correct jumper positions for the
desired ac input supply voltage. The multi-tap
ac input voltage setting can be verified without
removing the safety shield.
• Open ATevo's front door and locate
the Multi-Tap terminal block above
the AC Input Breaker (CB1).
• Observe the relative locations of the
RED jumpers in the Multi-Tap terminal
block (TB-H#).
• Refer to the adjacent diagram to
confirm the present ac input voltage
setting is correct.
Before changing the voltage selection
ATevo
2 Wiring
15