HindlePower ATevo Series Operating/Service Instructions Manual page 33

Microprocessor-controlled float battery charger
Hide thumbs Also See for ATevo Series:
Table of Contents

Advertisement

NOTES
• Conduit must be properly grounded, and in compliance with the
national wiring rules of the country where installed.
• Use copper or aluminum conductors only.
• For 120 Vac, connect the neutral leg to input terminal (CB1-L2).
PROCEDURE
1. Remove safety shield per Section 2.2.
2. Run ac input supply wiring into ATevo, ending at the AC Input
Circuit Breaker (CB1) and ground stud.
3. Connect wires to appropriate locations on AC Input Circuit
Breaker (CB1-L1/L2) and system ground stud, as indicated on
drawing.
4. Using a flat-blade screwdriver, securely tighten the compression
screws on AC Breaker (CB1-L1/L2).
5. Securely tighten ground wire on system ground stud.
6. Check all connections and reinstall safety shield.
ATevo
2 Wiring
17