CHARGER MODE
'Float' = FLOAT
MODE
'Equalize' =
EQUALIZE MODE

4.2 Configuring Basic Set Points and Alarms

The ATevo is the second generation of AT Series microprocessor-
controlled float battery chargers. Because its configuration button
sequence is identical, users of legacy AT10.1 chargers will easily
adapt to the ATevo. This section details how to configure basic ATevo
set points, and alarms found also on legacy AT10.1 chargers:
• Float Voltage
• Equalize Voltage
• Equalize Timer
• High DC Voltage Alarm
• Low DC Voltage Alarm
• Current Limit Level

4.2.1 How to Configure General Parameter Settings

You can adjust ATevo settings during operation using the front panel
controls. When you first press EDIT/ENTER, ATevo prompts you to set
the first parameter in the list (Float Voltage).
To set parameters, do the following:
• Press UP or DOWN (or hold down to scroll) until desired value
displays. Each parameter has a minimum and maximum limit as
listed in the tables in Section 4.1.2.
• Press EDIT/ENTER to save setting. ATevo prompts you to set the
second parameter.
• Continue in the same manner to set all six (6) parameters in the list.
If you want to skip setting any parameter, press EDIT/ENTER (or
RIGHT arrow) to bypass it.
• When finished setting the sixth parameter (Current Limit), press EDIT/
ENTER to save setting and return to normal operation.
• Any changes that you have made take effect immediately. ATevo uses
its last saved values if it is powered down and returned to service.
4 Startup & Configuration
ATevo
EQUALIZE METHOD
'Man' = MANUAL
TIMER
'Auto' =
AUTOMATIC TIMER
37