Auxiliary I/O Board Relay Configuration - HindlePower ATevo Series Operating/Service Instructions Manual

Microprocessor-controlled float battery charger
Hide thumbs Also See for ATevo Series:
Table of Contents

Advertisement

12 Auxiliary Inputs/Outputs
Auxiliary I/O Board Relays can be mapped to indicate the state of
any ATevo alarm or status point. Each relay can be independently
configured to latch when the alarm or status point associated with
the relay becomes active. Once latched, the relay must be cleared
manually by initiating the RESET LATCHED RELAY feature (see
Section 7.6). All relays have a time delay configuration. The relay
will not change to active state until the associated alarm or status
point has changed to active state and remains in active state for the
configured time delay.
NOTICE
Software Configuration Naming
In the following subsections, Auxiliary I/O Board relays are specified
by "A4" board number (see Section 12.3.1), and relay number on the
associated board. For example: 'Aux 1 relay 3' specifies Relay #3 on
Auxiliary I/O Board #1.

12.4.1 Auxiliary I/O Board Relay Configuration

To make changes to parameters for a relay on the Auxiliary I/O
Board:
MENU > RELAYS > 'Relay Configuration' > select relay from options >
select parameter as shown in Section 12.4.2 through 12.4.4
107